System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321 Page 23
REGISTER
ADDRESS
DESCRIPTION REGISTER TYPE
READ/
WRITE
COMMENT
41059 Mass Total –Lbs Floating point register (1 of 2) Read Only
Mass units are only
available when using
F-2000 Vortex meter
41060 Mass Total –Lbs Floating point register (2 of 2) Read Only
41061 Mass Total –kg Floating point register (1 of 2) Read Only
41062 Mass Total –kg Floating point register (2 of 2) Read Only
41063 Auxiliary Input Total (Di3) Floating point register (1 of 2) Read Only
41064 Auxiliary Input Total Floating point register (2 of 2) Read Only
41065 Zero Mode 1 Energy Total 0 – 1 0 – 1
Not
applicable
Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of zero
to the register once the
totals reset.
41066 Zero Mode 1 Volume Total 0 – 1 0 – 1
Not
applicable
Read/Write
41067 Zero Mode 2 Energy Total 0 – 1 0 – 1
Not
applicable
Read/Write
41068 Zero Mode 2 Volume Total 0 – 1 0 – 1
Not
applicable
Read/Write
41069 Zero Auxiliary Input Total (Di3) 0 – 1 0 – 1
Not
applicable
Read/Write