System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321 Page 16
8. When the address change is complete, the following message will appear.
You must cycle power to the System-10 for the change to take effect.
1.6.3 Changing the Gateway Address
Changing the gateway address requires the use of RUInet utility software and a PC with
an Ethernet card and an available port. Assuming the meter is programmed with the
default IP address (192.168.1.24), the host PC must be congured with an IP address of
192.168.1.1 and a subnet mask of 255.255.255.0. RUInet is available for download from
the ONICON web site, www.onicon.com.
1. Load RUInet and congure the PC as necessary.
2. Connect an RJ45 Ethernet cable between the PC and the display and power the
System-10. Allow 60 seconds for the display rmware to cycle through start-up
diagnostic routines.
3. Open RUInet.
4. From the Remote User Interface main menu (shown below) select option “I”,
Change IP Address.
Vue de la page 15