SECTION 2.0: MODBUS MEMORY MAP
ONICON Btu meters equipped with MODBUS serial communications provide energy and volume rate
data, and totalized energy and volume data in a variety of engineering units. You select the engineering
units you wish to use by mapping to the appropriate registers.
Also supplied with your System-10 is a document titled “Recommended MODBUS Conguration
Data”. This document is different for each Btu meter. It provides a suggested list of registers to use. The
recommendations are based on the calibration of the ow meter and the programming of units and
multipliers displayed on the System-10.
2.1 MODBUS REGISTER FORMAT AND NETWORKING INFORMATION
1. All registers are 16 bit MODBUS Holding Registers.
2. MODBUS Holding Registers are used in 4 different ways.
A. As an Analog Value: In some cases these values are scaled
by multiplying the register contents by a xed multiplier.
B. As a status indicator where the register value can only
be “1” or “2”.
C. As a mode indicator where the value indicates current operating mode
such as “1” = single, “2” = dual, or “3” = bi-directional.
D. As a control register where the host can write a value to reset total(s).
3. Registers 40001 through 40068 are unsigned integer registers (0 to 65,535) except for 40024
and 40025. These are 16 bit signed integer values (-32,768 to +32,767). Registers 41003
through 41081 are 32 bit single precision oating point values. 41001, 41002 and 41065
through 41069 are unsigned integer registers.
4. System-10 MODBUS register addresses are formatted as follows:
Example: address 40001
4 = Holding register
0001 = Address that corresponds to memory location 0000
5. MODBUS function codes supported:
CODE DESCRIPTION
03 Read Holding Registers
06 Preset Single Registers
16 Preset Multiple Registers
17 Report Slave ID
i
IMPORTANT NOTE
ONICON provides data in integer and oating point format. We recommend the use of oating
point registers to transmit data to the network. The use of oating point data eliminates the need
for scaling and additional mathematical operations to totalize energy and ow.