CAUTION
Failure to provide a proper earth connection to the meter may result in excessive electrical
noise that will interfere with the operation of the meter.
Wire Color Description Notes
Red (+) Supply voltage: 24±4 VDC @ 250 mA or 24±4 VAC,
60 Hz, 6 VAC
Connect to power supply (+): DC (+) or
AC (line)
Black (-) Isolated supply voltage common Connect to power supply (-): DC (-) or
AC (neutral)
Green / Yellow Earth ground connection Required to operate the meter
Green (+) Isolated frequency output Required when connecting to ONICON
display or BTU meter
Yellow (-) Frequency output common
Blue (+) Isolated analog output Congurable as a 4-20 mA, 0-10 V or
0-5 V output
Brown (-) Isolated analog output common
Gray Forward ow, scaled output, isolated dry contact Scalable dry contact pulse output for
forward ow totalization
Violet
Gray / Black Reverse ow, scaled output, isolated dry contact Scalable dry contact pulse output for
reverse ow totalization
Violet / Black
Orange / Black Flow direction indicator, isolated dry contact Contact closed when ow is in direction
of arrow on meter
White / Black
Diagnostic Signals
Orange Master alarm, isolated dry contact Dry contact closure signal indicating
fault condition
White
3.5.1 Signal and Power Wiring Connections
½" FNPT
conduit connection
Insertion depth
gage provided
with each meter
FLOW
Customer provided
conduit and adapters
Output signal(s)
to control
system
ONICON
Display or
BTU Meter
(Optional)
Allow enough slack
in the flexible conduit
to permit the meter
to be removed
from the valve.