3.3.2.2 Input Signal Connections From Insertion Turbine Flow Meters
ONICON turbine ow meters are provided with a number of different output
congurations. These affect the number of wires contained in the cable attached
to the ow meter. Refer to the diagram below and the laminated tag attached to
the ow meter for specic details.
Connections shown with (E)
are used with F-x30 models, including
bi-directional.
Connections shown with (D)
are used with F-x11 models, including
bi-directional.
Connections shown with (C)
are used with F-x10 models, including
bi-directional.
(D) Isolated Analog Common - (Yellow)
Connections shown are for flow meter
output signals not used by the Btu meter.
Both incoming and outgoing connections
are made to the same terminal.
Auxiliary Flow Meter Signals
* Shield
(C) Analog Common - (Black)
Flow Meter Inputs
For F-1x10, F-1x11 & F-1x30
(E) Scaled - (Brown)
(E) Scaled + (Blue)
(C or D) 0-10 VDC + (Brown)
(C or D) 4-20mA + (Blue)
Connections shown with (B)
are required for all dual turbine models,
including bi-directional.
Connections shown with (A)
are required for all
bi-directional models.
Connections shown with * are
required for all models.
F-1100, F-1200 & F-1300 Series
Flow Meter Connections
(B) Bottom Turbine (Orange)
(B) Top Turbine (White)
(A) Direction - (Violet)
(A) Direction + (Grey)
* Frequency + . (Green)
* Supply Common - (Black)
* 24VDC Supply + (Red)
J1
5
G
60HZ
1
J2-1
+15
+24
J2-12
G
G
10
R7
H3
R1
20075-50 REV. A
LED1
T1
D1
D2
VAR1
F1
1/8 AMP
TB1
D4
D3
H1
1
Factory Installed Cable
L1 N Not Used
* 4-20mA -
* 4-20mA +
F-2000 Flow Meter
Connections
(A) Scaled +
(A) Scaled -
Flow Meter Inputs
* Shield
Auxiliary Flow Meter Signals
* Earth
Outputs Terminal #
* + 24V
* - ILoop
+ 24V
- Pout
* Earth
Connections shown with * are required for all installations. Connections shown with (A) are optional.
1
2
3
4
L1 N Not Used
3.3.2.3 Input Signal Connections From F-2500 Flow Meters