System-10 BTU Meter Manual 03/15 - 0651-16 / 18323 Page 17
OPERATING FROM 24 VAC POWER
IMPORTANT NOTE
This option is not eld selectable. Contact ONICON if you need to change the input voltage rating.
i
The SYSTEM-10 BTU Meter can be congured to operate from 24 ±4 V 50/60 Hz power.
Connect the 24 volt power source to the System-10 using the pre-drilled conduit or strain
relief opening located at the bottom of the enclosure. Do not connect the 24 volt source
until all signal connections have been made and veried. Connect 24 VAC wires to the
appropriate screw terminals as shown. Connect the protective earth wire as shown. Do not
exceed 13 in-lb (1.5 Nm) of torque when tightening.
As power is initially applied to the System-10, immediately conrm that the power light is
illuminated and the display is scrolling through the character diagnostic test. The test will
begin by indicating the letter P in every position followed by a countdown from 9 to 0 for
each digit. If this does not occur, disconnect power immediately and re-verify all wiring
connections. Contact ONICON if the problem persists.
!
J1
5
G
60HZ
1
J2-1
+15
+24
J2-12
G
G
10
R7
H3
R1
20075-50 REV. A
LED1
T1
D1
D2
VAR1
F1
TB1
D4
D3
H1
1
R1
20075-50 REV. A
F1
TB1
3/4 AMP
3/4 AMP
L1 N Not Used
L1 N Not Used
CAUTION
This product must be connected to earth ground for proper operation. Failure to do so may result
in erratic operation.
Protective Earth
Ground