SECTION 2.0: BACnet PICS AND OBJECTS
2.1 PIC STATEMENTS
SYSTEM-10 BTU METER BACNET DRIVER
Protocol Implementation Conformance Statement (PICS)
BACnet Protocol
Date: August 16, 2005
Vendor Name: ONICON Incorporated
Product Name: System-10 Btu Meter
Product Model: SYSTEM-10-BAC
Product Description: The System-10 BTU Meter provides highly accurate thermal energy measurement in chilled water, hot water and condenser water
systems based on signal inputs from two matched temperature sensors (included) and any of ONICON's insertion or inline flow meters (ordered separately). The
System-10-BAC provides energy, flow and temperature data on a local alphanumeric display and to the network via the BACnet communications MS/TP driver.
An optional auxiliary input is also available to totalize pulses from another device and communicate the total directly to the network.
BACnet Standardized Device Profile (Annex L):
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
K.1.2 BIBB – Data Sharing – ReadProperty-B (DS-RP-B)
K.1.8 BIBB – Data Sharing – WriteProperty-B (DS-WP-B)
K.5.2 BIBB – Device Management – Dynamic Device
Binding-B (DM-DDB-B)
Segmentation Capability:
None
Standard Object Types Supported:
Device Object
Multi State Input Output
Analog Input
Multi State Output
Analog Output
Multi State Value
Analog Value
Binary Input
Binary Output
Binary Value
For all these properties the following apply:
1. Does not support BACnet CreateObject
2. Does not support BACnet DeleteObject
3. Does not support any optional properties
4. No additional writeable properties exist
5. No proprietary properties exist
6. No range restrictions exist
Data Link Layer Options:
MS/TP master (Clause 9), baud rate up to 76800 bps
MS/TP slave (Clause 9), baud rate up to 76800 bps
Device Address Binding:
Not supported
Character Sets Supported:
ANSI X3.4.