REGISTER
ADDRESS
DESCRIPTION REGISTER TYPE READ / WRITE COMMENT
313 Flow Total - part 1 Long Integer (1 of 2) Read / Write Write 0 to reset
total.
314 Flow Total - part 2 Long Integer (2 of 2) Read / Write
REGISTER
ADDRESS
DESCRIPTION REGISTER TYPE READ / WRITE COMMENT
579 Flow Rate - part 1 Floating Point (1 of 2) Read Only
580 Flow Rate - part 2 Floating Point (2 of 2) Read Only
581 Temperature - part 1 Floating Point (1 of 2) Read Only
582 Temperature - part 2 Floating Point (2 of 2) Read Only
583 Zero Cal. - part 1 Floating Point (1 of 2) Read Only
584 Zero Cal. - part 2 Floating Point (2 of 2) Read Only
REGISTER
ADDRESS
DESCRIPTION REGISTER TYPE READ / WRITE COMMENT
835 Flow Rate - part 1 Scaled Long Integer (1 of 2) Read Only
Multiply long
integer by .001 to
read value.
836 Flow Rate - part 2 Scaled Long Integer (2 of 2) Read Only
837 Temperature - part 1 Scaled Long Integer (1 of 2) Read Only
838 Temperature - part 2 Scaled Long Integer (2 of 2) Read Only
839 Zero Cal. - part 1 Scaled Long Integer (1 of 2) Read Only
840 Zero Cal. - part 2 Scaled Long Integer (2 of 2) Read Only