F-3200 Flow Meter Manual 05/14 - 0671-12 / 18325 Page 8
1.4 STANDARD FEATURES AND SPECIFICATIONS
A built-in user interface & graphic display
A single 4 – 20mA output for ow rate
Two programmable open collector pulse outputs. Outputs may be programmed to provide:
* an indication of ow direction
* a scaled pulse for totalizing ow
* a high resolution frequency output to drive peripheral devices
* an indication of an alarm condition
Empty pipe detector
Internal self-diagnostic functions & fault alarms
CALIBRATION
Flow meters are wet calibrated in a ow laboratory
against standards that are directly traceable to
government standards. A certicate of calibration
accompanies every meter.
ACCURACY
Accurate to within:
± 0.2% of reading from 1.6 to 33 ft/s
± 0.0033 ft/s at ows less than 1.6 ft/s
PROGRAMMING
Factory programmed for specic application
MEMORY
Nonvolatile memory retains all program parameters
and totalized values in the event of power loss.
DISPLAY
Alphanumeric LCD displays total ow, ow rate,
ow direction & alarm conditions
OUTPUT SIGNALS
Isolated 4 – 20mA analog output for ow rate
2 isolated programmable opto-coupled open
collector digital/pulse outputs
(Congurable for frequency, pulse, alarm or
directional ow)
40VDC, 100mA and 1250Hz maximum
(Optional) Redundant output option with second
isolated analog output for ow rate and 2 additional
isolated programmable opto-coupled open collector
digital/pulse outputs
(Pulse outputs congurable for frequency, pulse,
alarm or directional ow)
40VDC, 100mA and 1250Hz maximum
TEMPERATURE RANGE
Liquid temperature range:
Polypropylene liner: 32° to 140°F
Ebonite liner: 23° to 175°F
PTFE liner: -4° to 212° F (266° F with remote
electronics without pre-amplier option)
Ambient temperature range: -4° to 140°F
FLUID CONDUCTIVITY
5 µS/cm minimum
MAINTENANCE
Periodically inspect the power supply cables,
cable glands and the enclosure for signs of
damage. Inspect installation and mounting hardware
for loose connections.
MECHANICAL
Electronics Enclosure:
Standard: Painted Aluminum NEMA 6
(Optional) Remote mount w/o pre-amplier,
maximum distance from sensor - up to 325 ft @
conductivities ≥ 200µS/cm
Remote mount transmitter with pre-amplier in
sensor body (maximum distance from sensor
body, 1640ft).
Outer Body Material:
Standard: Carbon Steel, Painted
Optional: 316 Stainless Steel
Flow Tube (Internal):
304 Stainless Steel
Connection Type:
Standard: ANSI 150 Class Flange
Optional: ANSI 300 Class Flange
Optional: Wafer
Optional: Threaded Process Connection
ELECTRICAL
This equipment is intended for INSTALLATION
CATEGORY (OVERVOLTAGE CATEGORY) II
applications.
Input Power - Factory Selectable:
Standard - 100 - 240 VAC, 45 - 66 Hz, 12 VA typical
Optional - 18 - 45 VDC, 10 W typical
OR 18 - 45 VAC, 45 - 66 Hz, 12 VA typical
Overcurrent Protective Device Ratings:
Supply mains overcurrent protective devices with
the following ratings:
• 120VAC 50/60 Hz – 15 A
• 230VAC 50 Hz – 6 A
Wiring:
Flow signals - Use 18-22 AWG shielded cable
Standard input power - Use a three wire service
with one wire a protective earth ground. The
installation must comply with all local, state and
federal building codes.
Optional input power - Use PVC jacketed copper
cable with a wire gauge suitable for the length of
run and required maximum current carrying
capacity. The installation must comply with all
local, state and federal building codes.
Note: Specications are subject to change without notice.